SAMPLE SPECIFICATION*
1.0 PRODUCT DESCRIPTION
FlowGuard Gold® CPVC pipe and fittings are extruded/molded from
CPVC compounds manufactured by Lubrizol. The pipe compound shall meet
cell class 24448 and the fitting compound shall meet cell class
23447 as defined by ASTM D1784. Both the pipe and the fitting compounds
shall be certified by NSF International for use with potable water.
1.1 PIPE AND FITTINGS
Pipe and fittings shall meet or exceed the requirements of ASTM
D2846.
1.2 SOLVENT CEMENT
All socket type joints shall be assembled employing solvent cements
that meet or exceed the requirements of ASTM F493. The standard
practice for safe handling of solvent cements shall be in accordance
with ASTM F402. Solvent cement shall be listed by NSF International
for use with potable water, and approved by the FlowGuard Gold®
pipe and fittings manufacturers.
1.3 BASIC USE
2.0 MATERIALS
The piping systems shall be constructed from materials extruded/molded
by manufacturers using FlowGuard Gold® CPVC compound.
2.1 MANUFACTURERS
| A. PIPE AND/OR FITTINGS | |
|
Bow Industrial Corp. |
Charlotte Pipe and Foundry Co. |
|
Cresline Plastic Pipe Co. |
Genova Products, Inc. |
|
NIBCO, Inc. |
|
| B. BALL VALVES | |
|
King Bros. Industries |
NIBCO, Inc. |
| C. SOLVENT CEMENTS | |
|
Fry Technology |
IPS Corporation |
|
Schwartz Chemical of Canada Ltd. |
The Oatey Company |
3.0 SYSTEM DESIGN
3.1 INSTALLATION PROCEDURES
Installation practices such as pipe support spacing, bracing, allowance
for thermal expansion/contraction, solvent cementing and handling
and storage shall be in accordance with the manufacturer’s
instructions and this specification.
3.2 LIMITATIONS
FlowGuard Gold® pipe and fittings are intended for use at a
maximum working pressure of 100 psi at 180°F (400 psi at 73°F).
3.3 TECHNICAL DATA
A. APPLICABLE STANDARDS
B. APPLICABLE CODES
3.4 TESTING
After the system is installed and any solvent cement is cured, the
system shall be hydrostatically tested per the manufacturer’s
installation instructions and the requirements of the applicable
plumbing or mechanical code.
3.5 WARRANTY
Consult the manufacturer for specific Warranty information.
*Not intended to be a stand alone specification. The above specification is intended to be added within your company’s standard plumbing specifications to specify the use of FlowGuard Gold® CPVC pipe and fittings.